Citation

Ferkl Lukáš and Široký Jan : Ceiling radiant cooling: Comparison of ARMAX and subspace identification modelling methods . BUILDING AND ENVIRONMENT, vol. 2010, p. 205-212, PERGAMON-ELSEVIER SCIENCE LTD, THE BOULEVARD, LANGFORD LANE, KIDLINGTON, OXFORD OX5 1GB, 2010.

Abstract

The building of the Faculty of Mechanical Engineering, Czech Technical University in Prague - Dejvice, has been heated by a ceiling radiant heating system ("Crittall" system) since 1961. One building block has been equipped by means which enable the use of the pipes of the radiant heating system for ceiling radiant cooling. As optimization of this system is desired, the first step to be performed is the identification. Because of a complicated physical description of the entire system, and a set of measured data which is large enough to perform statistical identification, a decision was made to identify the system by ARMAX model identification and subspace identification methods. The resulting identified model shows a standard deviation of 0.2-0.3 degrees C on the verification data. The model identified by the subspace methods, enhanced by a Kalman filter, shows a standard deviation of 0.063 degrees C for output tracking. Such a model is ready to be used in modern multidimensional controllers, such as model-based predictive controllers (MPC).

Detail of publication

Title: Ceiling radiant cooling: Comparison of ARMAX and subspace identification modelling methods
Author: Ferkl Lukáš ; Široký Jan
Language: English
Year: 2010
Type of publication: Papers in journals
Title of journal or book: BUILDING AND ENVIRONMENT
Číslo vydání: 2010
Page: 205 - 212
ISSN: 0360-1323
Publisher: PERGAMON-ELSEVIER SCIENCE LTD
Address: THE BOULEVARD, LANGFORD LANE, KIDLINGTON, OXFORD OX5 1GB
2011-03-15 16:21:55 / 2011-03-15 16:21:55 / 1

Keywords

Cooling, Building management systems, System identification, Subspace methods, ARMAX, Modelling

BibTeX

@ARTICLE{FerklLukas_2010_Ceilingradiant,
 author = {Ferkl Luk\'{a}\v{s} and \v{S}irok\'{y} Jan},
 title = {Ceiling radiant cooling: Comparison of ARMAX and subspace identification modelling methods},
 year = {2010},
 publisher = {PERGAMON-ELSEVIER SCIENCE LTD},
 journal = {BUILDING AND ENVIRONMENT},
 address = {THE BOULEVARD, LANGFORD LANE, KIDLINGTON, OXFORD OX5 1GB},
 volume = {2010},
 pages = {205-212},
 ISSN = {0360-1323},
 note = {vr\'{a}ceno na \v{z}\'{a}dost KKY, ve WoS ani u \v{c}l\'{a}nku nen\'{i} autor ve vazb\v{e} na Z\v{C}U.},
 url = {http://www.kky.zcu.cz/en/publications/FerklLukas_2010_Ceilingradiant},
}